Home Analyst, Inc.
P.O. Box 670774 |
|||||||
Customer |
|||||||
Home |
|||||||
Real Estate Agent |
|||||||
|
|||||||
|
|||||||
| Date: 9/19/2006 | Time: 11:24 PM | Report ID: 06091901-Framed Home Example |
| Property: 5875 New Home Court Lot #99 Marietta, GA 30066 |
Customer: Thomas Hombuyer |
Real Estate Professional: |
| Client Is Present: Yes | Age Of Home: New Construction | Radon Test: No |
| Water Test: No | Weather: Clear | Temperature: Over 80 |
| Rain in last 3 days: No |
GAHI Limitations for Structural Components
The Inspector is not required to:
| FOUNDATION: POURED CONCRETE | FLOOR STRUCTURE: ENGINERED FLOOR TRUSS | WALL STRUCTURE: 2 X 4 WOOD 2 X 6 WOOD |
| COLUMNS OR PIERS: SUPPORTING WALLS | ROOF STRUCTURE: STICK-BUILT 2 X 6 RAFTERS 2 X 8 RAFTERS LATERAL BRACING SHEATHING | ROOF-TYPE: GABLE HIP |
| IN | NI | NP | C | RR | ||
| 1.0 | FOUNDATIONS (Structural) | X | X | X | ||
| 1.1 | FLOORS (Structural) | X | X | X | ||
| 1.2 | WALLS (Structural) | X | X | X | ||
| 1.3 | CEILINGS (Structural) | X | X | |||
| 1.4 | ATTIC AND ROOF STRUCTURE | X | X | X | ||
| IN | NI | NP | C | RR | ||
CODE ICC R502.12 Draftstoppining required. When there is usable space both above and below the concealed space of a floor/ceiling assembly, draftstops shall be installed so that the area of the concealed spaced does not exceed 1,000 square feet. Draftstopping shall divide the concealed space into approximately equal areas. Where the assembly is enclosed by a floor membrane above and a ceiling membrane below draftstopping shall be provided in floor/ceiling assemblies under the following circumstances:
1. Ceiling is suspended under the floor framing.
2. Floor framing is constructed of truss-type open-web or perforated members.
R.502.12.1 Materials. Draftstopping materials shall be no less than 1/2-inch gypsum board, 3/8-inch wood structural panels, 3/8-inch Type 2-M-W particle board or other approved materials and adequately supported. Draftstopping shall be installed parallel to the floor framing members unless otherwise approved by the building official. The integrity of all draftstopping shall be maintained.
![]() 1.1 Picture 1 | ![]() 1.1 Picture 2 |
![]() 1.1 Picture 3 | ![]() 1.1 Picture 4 |
![]() 1.1 Picture 5 | ![]() 1.1 Picture 6 |
Website: Simpson Strong Tie. Joist Hangers, Tie Downs and Wall Anchorshttp://www.strongtie.com/
![]() 1.1 Picture 7 | ![]() 1.1 Picture 8 |
![]() 1.1 Picture 9 |
Damaged trusses were found above the upstairs bathroom. See photos for locations. Have the truss manufacturer submit in writing a diagram for the specific repair or have a qualified structural engineer design a repair.
Code ICC RR502.8.2 Engineered wood products. Cuts, notches and holes bored in trusses, laminated veneer lumber, glue-laminated members or I-joists are not permitted unless the effects of such penetrations are specifically considered in the design of the member.
![]() 1.1 Picture 10 | ![]() 1.1 Picture 11 |
CODE ICC R602.8 Fireblocking required. Fireblocking shall be provided to cut off all concealed draft openings(both vertical and horizontal) and to form an effective fire barrier between stories and between a top story and the roof space.
Fireblocking shall be provided in wood-frame construction in the following locations:
For details and/or examples see photo(s):
![]() 1.2 Picture 1 | ![]() 1.2 Picture 2 |
![]() 1.2 Picture 3 | ![]() 1.2 Picture 4 |
![]() 1.2 Picture 5 |
ICC CODE R602.3.1 Stud Spacing. In bearing walls, studs that are not more than 10 feet in length shall be spaced not more than is specified in Table R602.3.(5). In bearing walls, studs that are more than 10 feet in height shall be spaced not more than specified in Table R602.3.1.
![]() 1.2 Picture 6 | ![]() 1.2 Picture 7 |
![]() 1.2 Picture 8 |
CODE ICC R601.2 Requirements. Wall construction shall be capable of accommodating all loads imposed according to Section R301 and of transmitting the resulting loads to the supporting structural elements.
![]() 1.2 Picture 9 |
Code ICC RR602.3 Design and construction. Exterior walls of wood-frame construction shall be designed and constructed in accordance with the provisions of this chapter and Figure RR602.3(1) and Figure RR602.3(2) or in accordance with AF&PA's NDS. Components of exterior walls shall be fastened in accordance with Table RR602.3(1) through §RR602.3(4).
![]() 1.2 Picture 10 |
CODE ICC R602.4 Interior load-bearing walls. Interior load-bearing walls shall be constructed, framed and fireblocked as specified for exterior walls.
Code IRC R602.10 Wall bracing. Walls shall be braced in accordance with this section. For buildings in Seismic Design Categories D1 and D2, walls shall be constructed in accordance with the additional requirements of Sections R602.10.9 and R602.11.
Code IRC R602.10.1Braced wall lines.Braced wall lines shall consist of braced wall panel construction methods in accordance with Section R602.10.3. The amount and location of bracing shall be in accordance with Table R602.10.3 and the amount of bracing shall be the greater of that required by the Seismic Design Category or the design wind speed. Braced wall panels shall begin no more than 12.5 feet (3810 mm) from each end of a braced wall line. Braced wall panels that are counted as part of a braced wall line shall be in line, except that offsets out-of-plane of up to 4 feet (1219 mm) shall be permitted provided that the total out-to-out offset dimension in any braced wall line is not more than 8 feet (2438 mm). A designed collector shall be provided if the bracing begins more than 12 feet (3658 mm) from each end of a braced wall line.
![]() 1.2 Picture 11 |
![]() 1.3 Picture 1 |
ICC CODE R802.3 Framing details. Rafters shall be framed to ridge board or to each other with a gusset plate as a tie. Ridgeboard shall be at least 1-inch nominal thickness and not less in depth than the cut end of the rafter. At all valleys and hips there shall be a valley or hop rafter not less than 2-inches nominal thickness and not less in depth than the cut end of the rafter. Hip and valley rafters shall be supported at the ridge by a brace to a bearing partition or be designed to carry and distribute the specific load at that point. Where the roof pitch is less than three units vertical in 12 units horizontal , structural members that support rafters and ceiling joists, such as ridge beams, hips and valleys, shall be designed as beams.
![]() 1.4 Picture 1 |
GAHI Limitations for Grounds and Appurtenances
The Inspector is not required to:
GAHI Limitations for Building Exterior
The Inspector is not required to:
GAHI Limitations for Garage/Carport
The Inspector is not required to:
| SIDING STYLE: BRICK LAP | GARAGE LOCATION: ATTACHED | RETAINING WALLS: CONCRETE |
| SIDING MATERIAL: BRICK VENEER CEMENT-FIBER | WINDOW TYPES: THERMAL/INSULATED DOUBLE-HUNG WOOD |
| IN | NI | NP | C | RR | ||
| 2.0 | WALL CLADDING, FLASHING AND TRIM | X | X | X | ||
| 2.1 | WINDOWS | X | X | |||
| 2.2 | VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIOS, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building and it's systems) | X | X | X | ||
| 2.3 | FOUNDATION DRAIN | X | X | X | ||
| IN | NI | NP | C | RR | ||
For details and/or examples see photo(s):
CODE ICC R703.7.5 Flashing. Flashing shall be located beneath the first course of masonry above finished ground level above the foundation wall or slab and at other point of support, including structural floors, shelf angles and lintels when masonry veneers are designed in accordance with Section R703.7. See Section R703.8 for additional requirements.
CODE ICC R703.7.6 Weepholes. Weepholes shall be provided in the outside wythe of masonry walls at a maximum spacing of 33 inches on center. Weepholes shall not be less than 3/16 inch in diameter. Weepholes shall be located immediately above the flashing.
CODE ICC R703.8 Flashing. Approved corrosion-resistive flashing shall be provided in the exterior wall envelope in such a manner as to prevent entry of water into the wall cavity or penetration of water to the building structural framing components. The flashing shall extend to the surface of the exterior wall finish and shall be installed to prevent water from reentering the exterior wall envelope. Approved corrosion-resistant flashings shall be installed at all of the following locations:
![]() 2.0 Picture 1 |
![]() 2.0 Picture 2 |
![]() 2.1 Picture 1 | ![]() 2.1 Picture 2 |
![]() 2.1 Picture 3 | ![]() 2.1 Picture 4 |
![]() 2.1 Picture 5 |
CODE ICC R401.3 Drainage. Surface drainage shall be diverted to a storm sewer conveyance or other approved point of collection so as to not create a hazard. Lots shall be graded so as to drain surface water away from foundation walls. The grade away from foundation walls shall fall a minimum of 6 inches within the first 10 feet.
Exception: Where lot lines, walls, slopes or other physical barriers prohibit 6 inches of fall within 10 feet, drains or swales shall be provided to ensure drainage away from the structure.
![]() 2.2 Picture 1 |
CODE ICC R405.1 Concrete or masonry foundations. Drains shall be provided around all concrete or masonry foundations that retain earth and enclose habitable or useable spaces located below grade. Drainage tiles, gravel or crushed stone drains, perforated pipe or other approved systems or materials shall be installed at or below the area to be protected and shall discharge by gravity or mechanical means into an approved drainage system. Gravel or crushed stone drains shall extend at least 1 foot beyond the outside edge of the footing and 6 inches above the top of the footing and be covered with an approved filter membrane material. The top of open joints of drain tiles shall be protected with strips of building paper, and the drainage tiles or perforated pipe shall be placed on a minimum of 2 inches of washed gravel or crushed rock at least one seive size larger than the tile joint opening or perforation and covered with not less than 6 inches of the same material.
![]() 2.3 Picture 1 |
For location(s) see photo(s):
![]() 2.3 Picture 2 |
GAHI Limitations for Roof, Guttering and Other Roof Components
The Inspector is not required to:
| CHIMNEY (exterior): METAL FLUE PIPE | VIEWED ROOF COVERING FROM: BINOCULARS GROUND | ROOF COVERING: 3-TAB FIBERGLASS ARCHITECTURAL |
| ROOF STYLE: HIP GABLE | ROOF PITCH: STEEP | SKY LIGHT (S): NONE |
| FLASHING: ALUMINUM |
| IN | NI | NP | C | RR | ||
| 3.0 | ROOF COVERINGS | X | ||||
| 3.1 | FLASHINGS | X | X | X | ||
| 3.2 | SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS | X | X | |||
| IN | NI | NP | C | RR | ||
![]() 3.0 Picture 1 |
For details and/or examples see photo(s):
CODE ICC R905.2.8.4 Sidewall flashing. Flashing against a vertical sidewall shall be by the step-flashing method. Website: Roof Flashing http://www.ibacos.com/pubs/RoofFlashingGuidelines.pdf![]() 3.1 Picture 1 |
![]() 3.2 Picture 1 |
GAHI Limitations for Electrical
The Inspector is not required to:
| ELECTRICAL CONDUCTORS: BELOW GROUND ALUMINUM 220 VOLTS | PANEL TYPE: CIRCUITS | BRANCH WIRE 15 and 20 AMP: COPPER |
| WIRING METHODS: ROMEX |
| IN | NI | NP | C | RR | ||
| 4.0 | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS | X | X | X | ||
| 4.1 | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE | X | X | |||
| 4.2 | CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) | X | X | X | ||
| IN | NI | NP | C | RR | ||
CODE ICC E3508.2.2 Installation. The electrode shall be installed such that at least 8 feet of length is in contact with the soil. It shall be driven to a depth of not less than 8 feet except that, where rock bottom is encountered, the electrode shall be driven at an oblique angle not to exceed 45 degrees from the vertically or shall be buried in a trench that is at least 2.5 feet deep. The upper end of the electrode shall be flush with or below ground level unless the above ground end and the grounding electrode conductor attachment are protected against physical damage.
![]() 4.0 Picture 1 |
![]() 4.1 Picture 1 |
Jetted tub motor is not bonded to hot and cold water lines. Recommend bonding prior to drywall installation.
Code IRC / NEC E3509.1 General. Bonding shall be provided where necessary to ensure electrical continuity and the capacity to conduct safely any fault current likely to be imposed.
Code IRC / NEC E3509.4.4 Other devices. Equipment shall be bonded by approved devices, such as bonding-type locknuts and bushings.
For details and/or examples see photo(s):
![]() 4.2 Picture 1 | ![]() 4.2 Picture 2 |
GAHI Limitations for Heating and Cooling Equipment and Systems
The Inspector is not required to:
| IN | NI | NP | C | RR | ||
| 5.0 | CHIMNEYS, FLUES AND VENTS | X | X | X | ||
| IN | NI | NP | C | RR | ||
Vent connector (flue pipe) for the master bedroom fireplace does not have adequate upward slope.
Code ICC RG2426.10.8 (§FG503.10.8) Slope. A vent connector shall be installed without any dips or sags and shall slope upward toward the vent or chimney at least 0.25 inch per foot (6.35 mm/305 mm).
![]() 5.0 Picture 1 |
GAHI Limitations for Insulation and Ventilation
The Inspector is not required to:
| ATTIC VENTILATION: RIDGE VENTS SOFFIT VENTS PASSIVE |
| IN | NI | NP | C | RR | ||
| 6.0 | VENTILATION OF ATTIC AND FOUNDATION AREAS | X | X | |||
| IN | NI | NP | C | RR | ||
![]() 6.0 Picture 1 | ![]() 6.0 Picture 2 |
![]() Home Analyst, Inc.
P.O. Box 670774 |
Customer |
Property Address |
| 1.0 | FOUNDATIONS (Structural) | |
| Inspected, Code Requirement, Repair or Replace | ||
|
Narrow exterior wall(s) require
specialized construction, bracing and anchorage to lower levels and to
the foundation. Modify existing short wall sections to
comply with the code to ensure proper performance of wall(s) in high
wind situations for the following locations: Garage door walls For details and/or examples see photo(s): Code ICC R 602.10.6 Alternate braced wall panels. Alternate braced wall lines constructed in accordance with one of the following provisions shall be permitted to replace each 4 feet of braced wall panel as required by Section R602.10.4: 1. In one-story buildings, each panel shall have a length of not less than 2 feet 8 inches and a height of mot more than 10 feet. Each panel shall be sheathed on one face with 3/8-inch-minimum-thickness wood structural panel sheathing nailed with 8d common or galvanized box nails in accordance with Table R602.3(1) and blocked at all wood structural panel sheathing edges. Two anchor bolts installed in accordance with Figure R403.1(1) shall be provided in each panel. Anchor bolts shall be placed at panel quarter points. Each panel end stud shall have a tie-down device fastened to the foundation, capable of providing an uplift capacity of at least 1,800 pounds. The tie-down device shall be installed in accordance with the manufacturer's recommendations. The panel shall be supported directly on a foundation or on floor framing supported directly on a foundation which is continuous across the entire length of the braced wall line. This foundation shall be reinforced with not less than one No. 4 bar top and bottom. When the continuous foundation is required to have a depth greater than 12 inches, a minimum 12 inch continuous footing to turned down slab edge is permitted at door openings in the braced wall line. This continuous footing or turned down slab edge shall be reinforced with not less than one No. 4 bar top and bottom. This reinforcement shall be lapped 15 inches with the reinforcement required in continuous foundation located directly under the braced wall line. 2. In the first story of two-story buildings, each braced wall panel shall be in accordance with Item 1 above, except that the wood structural panel sheathing shall be provided on both faces. at least there anchor bolts shall be placed at one-fifth points, and tie-down device uplift capacity shall not be less than 3.000 pounds. |
||
|
Foundation form boards have not been
removed. This can attract termites and other detrimental
biological life forms to the house. Remove all form boards from
the foundation. CODE ICC R408.8 Removal of debris. The under-floor grade shall be cleaned of all vegetation and organic material. All wood forms used for placing concrete shall be removed before a building is occupied or used for any purpose. All construction materials shall be removed before a building is occupied or used for any purpose. |
||
|
Foundation anchor straps are not properly
installed at several locations. Ensure all foundation anchors are
installed and properly connected. CODE ICC R403.1.6 Foundation anchorage. The wood sole plate at exterior wall on monolithic slabs and wood sill plate shall be anchored to the foundation with anchor bolts spaced a maximum of 6 feet on center. Anchor bolts shall also be located within 12 inches from the ends of each plate section. Bolts shall be at least 1/2 inch in diameter and shall extend a minimum of 7 inches into masonry or concrete. Interior bearing wall sole plates on monolithic slab foundations shall be positively anchored with approved fasteners. A nut and washer shall be tightened on each bolt to the plate. Sills and sole plates shall be protected against decay and termites where required by Sections R322 and R323. Exception: foundation anchor straps, spaced as required to provide equivalent anchorage to 1/2-inch-diameter anchor bolts. Note: Simpson Strong tie require the use of #10 d galvanized 1 1/2 inch nails to be used. These can be readily identified by a 10 stamped on the nail head. These nails have stronger heads than normal framing, roofing or sheathing, nails. Website: Simpson Strong Tie. Joist Hangers, Tie Downs and Wall Anchorshttp://www.strongtie.com/ For details and/or examples see photo(s): |
||
|
Remove foundation form strap projections and seal ends with waterproof cement. |
||
| 1.1 | FLOORS (Structural) | |
| Inspected, Code Requirement, Repair or Replace | ||
|
Draftstopping was not observed. It
should be noted that specific area calculations were not made, however
according to the information given by the client each
floor level has approximately 1,500 square
feet. Insure that draftstopping is installed to
comply with the following code.
CODE ICC R502.12 Draftstoppining required. When there is usable space both above and below the concealed space of a floor/ceiling assembly, draftstops shall be installed so that the area of the concealed spaced does not exceed 1,000 square feet. Draftstopping shall divide the concealed space into approximately equal areas. Where the assembly is enclosed by a floor membrane above and a ceiling membrane below draftstopping shall be provided in floor/ceiling assemblies under the following circumstances: 1. Ceiling is suspended under the floor framing. 2. Floor framing is constructed of truss-type open-web or perforated members. R.502.12.1 Materials. Draftstopping materials shall be no less than 1/2-inch gypsum board, 3/8-inch wood structural panels, 3/8-inch Type 2-M-W particle board or other approved materials and adequately supported. Draftstopping shall be installed parallel to the floor framing members unless otherwise approved by the building official. The integrity of all draftstopping shall be maintained. |
||
|
Joist hangers were found missing in
multiple locations including, but not limited to: Sunroom to house band
joist, (unable to view sunroom exterior wall floor joist to sunroom
band joist connection recommend removing plywood panels and verifying
proper installation of joist hangers) |
||
|
Joist hangers were not properly nailed in
several locations: See photos for examples. Ensure that all
joist hangers are completely nailed as per manufacturer's (Simpson
Strong Tie) instructions. Website: Simpson Strong Tie. Joist Hangers, Tie Downs and Wall Anchorshttp://www.strongtie.com/ |
||
|
Damaged trusses were found above the upstairs bathroom. See photos for locations. Have the truss manufacturer submit in writing a diagram for the specific repair or have a qualified structural engineer design a repair. Code ICC RR502.8.2 Engineered wood products. Cuts, notches and holes bored in trusses, laminated veneer lumber, glue-laminated members or I-joists are not permitted unless the effects of such penetrations are specifically considered in the design of the member. |
||
| 1.2 | WALLS (Structural) | |
| Inspected, Code Requirement, Repair or Replace | ||
|
Ensure all through floor penetrations
(pipe, wires, etc.) are sealed with an approved fire-resistant
sealant or other methods to provide fireblocking. This is usually
done at or just prior to installation of insulation. CODE ICC R602.8 Fireblocking required. Fireblocking shall be provided to cut off all concealed draft openings(both vertical and horizontal) and to form an effective fire barrier between stories and between a top story and the roof space. Fireblocking shall be provided in wood-frame construction in the following locations:
For details and/or examples see photo(s): |
||
|
Ensure hat areas shone in photo between
the right garage attic and the floor /ceiling floor joists are properly
sealed to provide fire blocking and prevent air from attic moving
through joists for concern of heat and cooling / insulation. |
||
|
Framing members are cut too short and do
not properly transmit load to lower structural elements. Replace,
shim or make repairs as necessary.CODE ICC R601.2 Requirements.
Wall construction shall be capable of accommodating all loads imposed
according to Section R301 and of transmitting the resulting loads to
the supporting structural elements. |
||
|
Replace missing, damaged, removed or overstrained studs.
ICC CODE R602.3.1 Stud Spacing. In bearing walls, studs that are not more than 10 feet in length shall be spaced not more than is specified in Table R602.3.(5). In bearing walls, studs that are more than 10 feet in height shall be spaced not more than specified in Table R602.3.1. |
||
|
Header is missing above the master
bedroom fireplace. Recommend engineered design to ensure proper load
transfer to other structural members. CODE ICC R601.2 Requirements. Wall construction shall be capable of accommodating all loads imposed according to Section R301 and of transmitting the resulting loads to the supporting structural elements. |
||
|
Header over arched window does not rest
on jack studs. Recommend replacing header with a header that will
span existing opening and be supported by full length king and jack
studs. Code ICC RR602.3 Design and construction. Exterior walls of wood-frame construction shall be designed and constructed in accordance with the provisions of this chapter and Figure RR602.3(1) and Figure RR602.3(2) or in accordance with AF&PA's NDS. Components of exterior walls shall be fastened in accordance with Table RR602.3(1) through §RR602.3(4). |
||
|
Load bearing walls are not properly cross-braced in the basement area. Bowing some studs were noted.
CODE ICC R602.4 Interior load-bearing walls. Interior load-bearing walls shall be constructed, framed and fireblocked as specified for exterior walls. Code IRC R602.10 Wall bracing. Walls shall be braced in accordance with this section. For buildings in Seismic Design Categories D1 and D2, walls shall be constructed in accordance with the additional requirements of Sections R602.10.9 and R602.11. Code IRC R602.10.1Braced wall lines.Braced wall lines shall consist of braced wall panel construction methods in accordance with Section R602.10.3. The amount and location of bracing shall be in accordance with Table R602.10.3 and the amount of bracing shall be the greater of that required by the Seismic Design Category or the design wind speed. Braced wall panels shall begin no more than 12.5 feet (3810 mm) from each end of a braced wall line. Braced wall panels that are counted as part of a braced wall line shall be in line, except that offsets out-of-plane of up to 4 feet (1219 mm) shall be permitted provided that the total out-to-out offset dimension in any braced wall line is not more than 8 feet (2438 mm). A designed collector shall be provided if the bracing begins more than 12 feet (3658 mm) from each end of a braced wall line. |
||
| 1.3 | CEILINGS (Structural) | |
| Inspected, Repair or Replace | ||
|
Bottom board under header in foyer is
bowing and should be secured to the framing members above to prevent
cracking of drywall. See photo. |
||
| 1.4 | ATTIC AND ROOF STRUCTURE | |
| Inspected, Code Requirement, Repair or Replace | ||
|
Ridge board and multiple rafters are not supported properly. Located above the family room bow window. See photo.
ICC CODE R802.3 Framing details. Rafters shall be framed to ridge board or to each other with a gusset plate as a tie. Ridgeboard shall be at least 1-inch nominal thickness and not less in depth than the cut end of the rafter. At all valleys and hips there shall be a valley or hop rafter not less than 2-inches nominal thickness and not less in depth than the cut end of the rafter. Hip and valley rafters shall be supported at the ridge by a brace to a bearing partition or be designed to carry and distribute the specific load at that point. Where the roof pitch is less than three units vertical in 12 units horizontal , structural members that support rafters and ceiling joists, such as ridge beams, hips and valleys, shall be designed as beams. |
||
| 2.0 | WALL CLADDING, FLASHING AND TRIM | |
| Inspected, Code Requirement, Repair or Replace | ||
|
Weep holes are missing above lintels were stone works is placed.
For details and/or examples see photo(s): CODE ICC R703.7.5 Flashing. Flashing shall be located beneath the first course of masonry above finished ground level above the foundation wall or slab and at other point of support, including structural floors, shelf angles and lintels when masonry veneers are designed in accordance with Section R703.7. See Section R703.8 for additional requirements. CODE ICC R703.7.6 Weepholes. Weepholes shall be provided in the outside wythe of masonry walls at a maximum spacing of 33 inches on center. Weepholes shall not be less than 3/16 inch in diameter. Weepholes shall be located immediately above the flashing. CODE ICC R703.8 Flashing. Approved corrosion-resistive flashing shall be provided in the exterior wall envelope in such a manner as to prevent entry of water into the wall cavity or penetration of water to the building structural framing components. The flashing shall extend to the surface of the exterior wall finish and shall be installed to prevent water from reentering the exterior wall envelope. Approved corrosion-resistant flashings shall be installed at all of the following locations:
|
||
| 2.1 | WINDOWS | |
| Inspected, Repair or Replace | ||
|
Multiple window were found to be
significantly out of square. Weather-stripping would not seal the
resulting gaps found at both top sash and bottom sash locations. It was
noted on the window that failure to properly square and shim windows
will void the manufacturer's warranty. Adjust window frames to
square conditions so as to comply with manufacture's warranty and
windows will properly close and seal. |
||
|
Top window sash springs at near right rear corner will not support the sash. Repair or replace to ensure proper operation. |
||
| 2.2 | VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIOS, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building and it's systems) | |
| Inspected, Code Requirement, Repair or Replace | ||
|
Erosion is present in the back yard area
with significant rutting of hill sides and deposition of sediment in
the back yard area. Ensure that grading measures are made to
comply with the following code. CODE ICC R401.3 Drainage. Surface drainage shall be diverted to a storm sewer conveyance or other approved point of collection so as to not create a hazard. Lots shall be graded so as to drain surface water away from foundation walls. The grade away from foundation walls shall fall a minimum of 6 inches within the first 10 feet. Exception: Where lot lines, walls, slopes or other physical barriers prohibit 6 inches of fall within 10 feet, drains or swales shall be provided to ensure drainage away from the structure. |
||
| 2.3 | FOUNDATION DRAIN | |
| Inspected, Code Requirement, Repair or Replace | ||
|
The foundation drain at left rear corner is not
visible. Take action as necessary to ensure that the
foundation drains are open and will drain by gravity. These
drains provide a means for water pressure to be relieved from the
foundation. Failure to leave the foundation drains open may cause
flooding of the basement. CODE ICC R405.1 Concrete or masonry foundations. Drains shall be provided around all concrete or masonry foundations that retain earth and enclose habitable or useable spaces located below grade. Drainage tiles, gravel or crushed stone drains, perforated pipe or other approved systems or materials shall be installed at or below the area to be protected and shall discharge by gravity or mechanical means into an approved drainage system. Gravel or crushed stone drains shall extend at least 1 foot beyond the outside edge of the footing and 6 inches above the top of the footing and be covered with an approved filter membrane material. The top of open joints of drain tiles shall be protected with strips of building paper, and the drainage tiles or perforated pipe shall be placed on a minimum of 2 inches of washed gravel or crushed rock at least one seive size larger than the tile joint opening or perforation and covered with not less than 6 inches of the same material. |
||
|
Repair / Replace damaged foundation drain at right side of the house.
For location(s) see photo(s): |
||
| 3.1 | FLASHINGS | |
| Inspected, Code Requirement, Repair or Replace | ||
|
Chimney is not flashed properly. Recommend"Step and Cap flashing" be installed.
For details and/or examples see photo(s): CODE ICC R905.2.8.4 Sidewall flashing. Flashing against a vertical sidewall shall be by the step-flashing method. Website: Roof Flashing http://www.ibacos.com/pubs/RoofFlashingGuidelines.pdf |
||
| 3.2 | SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS | |
| Inspected, Repair or Replace | ||
|
Daylight visible around plumbing vent
boot. Recommend having roofer inspect to ensure water tight
integrity prior to installation of drywall. |
||
| 4.0 | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS | |
| Inspected, Code Requirement, Repair or Replace | ||
|
Ground wire and or ground rods are
exposed and not protected from physical damage. Recommend
lowering rods and trenching area until electrical inspections are
complete and back filling to protect the grounding system or taking
other measures to meet the NEC / ICC code listed below. CODE ICC E3508.2.2 Installation. The electrode shall be installed such that at least 8 feet of length is in contact with the soil. It shall be driven to a depth of not less than 8 feet except that, where rock bottom is encountered, the electrode shall be driven at an oblique angle not to exceed 45 degrees from the vertically or shall be buried in a trench that is at least 2.5 feet deep. The upper end of the electrode shall be flush with or below ground level unless the above ground end and the grounding electrode conductor attachment are protected against physical damage. |
||
| 4.1 | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE | |
| Inspected, Repair or Replace | ||
|
Branch wiring is resting on master
bedroom fireplace vent connector. See photo. Reroute
conductor to ensure proper clearance. |
||
| 4.2 | CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) | |
| Inspected, Code Requirement, Repair or Replace | ||
|
Jetted tub motor is not bonded to hot and cold water lines. Recommend bonding prior to drywall installation. Code IRC / NEC E3509.1 General. Bonding shall be provided where necessary to ensure electrical continuity and the capacity to conduct safely any fault current likely to be imposed. Code IRC / NEC E3509.4.4 Other devices. Equipment shall be bonded by approved devices, such as bonding-type locknuts and bushings.
For details and/or examples see photo(s): |
||
| 5.0 | CHIMNEYS, FLUES AND VENTS | |
| Inspected, Code Requirement, Repair or Replace | ||
|
Vent connector (flue pipe) for the master bedroom fireplace does not have adequate upward slope. Code ICC RG2426.10.8 (§FG503.10.8) Slope. A vent connector shall be installed without any dips or sags and shall slope upward toward the vent or chimney at least 0.25 inch per foot (6.35 mm/305 mm). |
||
| 6.0 | VENTILATION OF ATTIC AND FOUNDATION AREAS | |
| Inspected, Repair or Replace | ||
|
Recommend installing strip soffit vents
and insulation shields to ensure that the space between the roof
decking and insulation in the sunroom will properly vent. Current
construction will allow for only a few of the rafter channels to be
vented. |
||
Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2004 : Licensed To Home Analyst, Inc.
![]() Home Analyst, Inc.
P.O. Box 670774 |
Customer |
Property Address |
| 1.0 | FOUNDATIONS (Structural) | |
| Inspected, Code Requirement, Repair or Replace | ||
|
Ensure that when the concrete patio is
poured, that proper trenching / holes for footer are made where the
support posts for the sun room will bear. |
||
| 2.0 | WALL CLADDING, FLASHING AND TRIM | |
| Inspected, Code Requirement, Repair or Replace | ||
|
Ensure that flexible duct is properly enclosed and insulated. |
||
| 3.0 | ROOF COVERINGS | |
| Inspected | ||
|
Monitor top front gable peak to ensure that it does not split. |
||
Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2004 : Licensed To Home Analyst, Inc.
![]() Home Analyst, Inc.
P.O. Box 670774 |
|
INVOICE |
| Home Analyst, Inc.
P.O. Box 670774 Marietta, GA 30066 404-978-2266 Bruce@yourhomeanalyst.com Inspected By: Bruce Rickey |
Inspection Date: 9/19/2006
Report ID: 06091901-Framed Home Example |
| Customer Info: | Inspection Property: |
| Thomas Hombuyer
555 New Home Drive Alpharetta GA 30055 Customer's Real Estate Professional: |
5875 New Home Court Lot #99 Marietta, GA 30066 |
Inspection Fee:
| ||||||||||||||||||||
Tax $0.00 | ||||||||||||||||||||
| Total Price $385.00 |
Payment Method:Credit Card
Payment Status:Paid At Time Of Inspection
Note:
| Client's Name(s): Thomas Hombuyer |
| Client's Phone Numbers: 770-555-10108 770-555-1011 | Client's Email Address: thomashombuyer@yahoo.com |
| Client's Billing Address: 555 New Home Drive | Inspection Address: 5875 New Home Court Lot #99 |
| City, State, Zip: Alpharetta, GA 30055 | City, State, Zip: Marietta, GA 30066 |
| Date and Time of Inspection: 9/19/2006 11:24 PM | Total Fee: $385.00 |
This inspection report is a visual inspection of the readily accessible areas of the property listed above, in accordance with the terms and conditions contained in the following Inspection Agreement, which is part of and integral to this report. Additional items to be inspected, listed above, are also covered by the Inspection Agreement. Failure to attend and participate limits the client’s full benefits of the inspection. Use of the written report and payment constitutes acceptance of the terms and conditions for non-attending clients. The inspection is not technically exhaustive and conforms to the Georgia Association of Home Inspectors Standards of Practice. It is the responsibility of the client to read completely the remarks printed on each page of the report. |
| INSPECTION AGREEMENT |
||||||||||||
Home Analyst, Inc. (the Company) agrees to conduct a limited visual inspection for the purpose of informing the Client of defects in the condition of the property, subject to the release and limitation of liability listed below. The inspection and report(s) are performed for the sole, confidential and exclusive use and possession of the Client. The written report(s) will include the additional items listed above and the following items only: |
||||||||||||
|
||||||||||||
It
is understood and agreed that this inspection will be of readily
accessible areas of the building and is limited to visual observation
of apparent conditions existing at the time of the inspection
only. Latent and concealed defects and deficiencies are excluded
from the inspection; equipment, items and systems will not be
dismantled. Maintenance and other items may be discussed, but
they are not a part of this inspection. The report is not a
compliance inspection or certification for past or present governmental
codes or regulations of any kind. |
||||||||||||
| Release and Limitation of Liability |
||||||||||||
It
is understood and agreed that the Company is not an insurer and that
the inspection and report are not intended or to be construed as a
guarantee or warranty of the adequacy, performance or condition of any
structure, item or system at the property address. The Client
hereby releases and exempts the Company and its agents and employees of
and from all consequential damage or personal injury of any
nature. |
________________________________________ Home Analyst, Inc. Date |
________________________________________ Client Date |
|
For details and/or examples see photo(s):
Code ICC R 602.10.6 Alternate braced wall panels. Alternate braced wall lines constructed in accordance with one of the following provisions shall be permitted to replace each 4 feet of braced wall panel as required by Section R602.10.4:
1. In one-story buildings, each panel shall have a length of not less than 2 feet 8 inches and a height of mot more than 10 feet. Each panel shall be sheathed on one face with 3/8-inch-minimum-thickness wood structural panel sheathing nailed with 8d common or galvanized box nails in accordance with Table R602.3(1) and blocked at all wood structural panel sheathing edges. Two anchor bolts installed in accordance with Figure R403.1(1) shall be provided in each panel. Anchor bolts shall be placed at panel quarter points. Each panel end stud shall have a tie-down device fastened to the foundation, capable of providing an uplift capacity of at least 1,800 pounds. The tie-down device shall be installed in accordance with the manufacturer's recommendations. The panel shall be supported directly on a foundation or on floor framing supported directly on a foundation which is continuous across the entire length of the braced wall line. This foundation shall be reinforced with not less than one No. 4 bar top and bottom. When the continuous foundation is required to have a depth greater than 12 inches, a minimum 12 inch continuous footing to turned down slab edge is permitted at door openings in the braced wall line. This continuous footing or turned down slab edge shall be reinforced with not less than one No. 4 bar top and bottom. This reinforcement shall be lapped 15 inches with the reinforcement required in continuous foundation located directly under the braced wall line.
2. In the first story of two-story buildings, each braced wall panel shall be in accordance with Item 1 above, except that the wood structural panel sheathing shall be provided on both faces. at least there anchor bolts shall be placed at one-fifth points, and tie-down device uplift capacity shall not be less than 3.000 pounds.
1.0 Picture 1
1.0 Picture 2
Foundation form boards have not been removed. This can attract termites and other detrimental biological life forms to the house. Remove all form boards from the foundation.
CODE ICC R408.8 Removal of debris. The under-floor grade shall be cleaned of all vegetation and organic material. All wood forms used for placing concrete shall be removed before a building is occupied or used for any purpose. All construction materials shall be removed before a building is occupied or used for any purpose.
1.0 Picture 3
1.0 Picture 4
Ensure that when the concrete patio is poured, that proper trenching / holes for footer are made where the support posts for the sun room will bear.
1.0 Picture 5
Foundation anchor straps are not properly installed at several locations. Ensure all foundation anchors are installed and properly connected.
CODE ICC R403.1.6 Foundation anchorage. The wood sole plate at exterior wall on monolithic slabs and wood sill plate shall be anchored to the foundation with anchor bolts spaced a maximum of 6 feet on center. Anchor bolts shall also be located within 12 inches from the ends of each plate section. Bolts shall be at least 1/2 inch in diameter and shall extend a minimum of 7 inches into masonry or concrete. Interior bearing wall sole plates on monolithic slab foundations shall be positively anchored with approved fasteners. A nut and washer shall be tightened on each bolt to the plate. Sills and sole plates shall be protected against decay and termites where required by Sections R322 and R323.
Exception: foundation anchor straps, spaced as required to provide equivalent anchorage to 1/2-inch-diameter anchor bolts.
Note: Simpson Strong tie require the use of #10 d galvanized 1 1/2 inch nails to be used. These can be readily identified by a 10 stamped on the nail head. These nails have stronger heads than normal framing, roofing or sheathing, nails.
Website: Simpson Strong Tie. Joist Hangers, Tie Downs and Wall Anchorshttp://www.strongtie.com/
For details and/or examples see photo(s):
1.0 Picture 6
1.0 Picture 7
Remove foundation form strap projections and seal ends with waterproof cement.